12' - 6" x 10' - 9" x 9' - 0" "T" Type Electrical Distribution Manhole
Typical Precast Concrete Manhole Installation
|
 |
 Concrete: 5,000 psi @ 28 days 5% - 8% entrained air Rebar: ASTM A-615 grade 60 epoxy coated Available duct entrances: Single duct terminators to accept5" Ø Sch 40 PVC conduit Design criteria: a) Meets ComEd* spec #C4381.B dated 5-1-95 and EM-14927 dated 9-1-92 b) ASTM C858 c) Loading per ASTM C857, including: -Earth cover: Min 1' - 0" Max 5' - 0" -AASHTO HS-20 wheel load & applicable impact -Vertical & lateral soil pressures determined using 120 PCF soil density -Ground water at 3' - 0" below grade c) Structural design performed using AASHTO strength design d) Reinforcing cover per ACI 318 Weight: a) Top section: 20,980# b) Base section: 20,340# c) Total manhole: 42,320#
|
 |

Item |
Description |
Qty. |
1 |
Cable rack inserts: 1/2" Ø 304 stainless threaded inserts each with 1/2" Ø x 2" 304 S hex head bolt, 1/2" SS washer and 1/2" PVC washer |
32 |
2 |
SS pulling irons |
3 |
3 |
4T lifting anchors |
8 |
4 |
20" Ø sump opening |
1 |
5 |
1" butyl rubber joint sealant |
5 rolls |
6 |
Rebar, epoxy coated |
|
7 |
5" Ø duct terminator |
54 |
8 |
1" Ø x 5-1/2" ground wire hole 1/2" KO |
2 |
9 |
1/4" Ø plastic threaded inserts 1/4" x 1" hex head SS bolt 1/4" x 1/4" Nylon Strap |
22 |
10 |
Ladder insert 3/8" Ø threaded carbon steel |
4 | |
 |