8' - 0" X 4' - 0" X 6' - 0" Type A Manhole
Typical Precast Concrete Manhole Installation
|
 |
 Concrete: 5,000 psi @ 28 days 5% - 8% entrained air Rebar: ASTM A-615 grade 60 Available duct entrances: a) Standard KO window b) 4" Ø duct terminator specify tele duct or sch 40 c) 5" Ø duct terminator sch 40 d) 6" Ø duct terminator sch 40 e) Custom configurations and/or locations Design criteria: a) ASTM C858 b) Loading per ASTM C857, Including: -Earth cover: Min 2' - 0" Max 5' - 0" -AASHTO HS-20 wheel load & applicable impact -Vertical & lateral soil pressures determined using 120 PCF soil density c) Ground water at 3' - 0" below grade d) Reinforcing cover per ACI 318 Weight: Top section: 6,795# Base section: 6,695# Total manhole: 13,490#
|
 |

Item |
Description |
Qty. |
1 |
1/2" Ø plastic cable rack inserts & 1/2" x 2-1/4" hex head bolts |
56 |
8 bonding ribbon assy's including: |
|
2 |
1/4" Ø x 1" inserts & hex bolts |
8 |
|
1/16" x 3/8" soft tinned copper bonding ribbon |
12' |
|
5/8" cable clamps |
8 |
3 |
Pulling irons: 1" Ø steel, hot dipped galvanized (provisions for two additional pulling irons) |
2 |
4 |
4T lifting anchors |
12 |
5 |
Sump depression w/ plastic lid |
1 |
6 |
1" butyl rubber joint sealant |
3 rolls |
7 |
Rebar |
| |
 |
 30" Ø Standard Manhole Frame and Cover Screen Friendly PDF Print Friendly PDF
Hardware Screen Friendly PDF Print Friendly PDF | |